China Testing Instruments Manufacturer,Whatsapp/Wechat:+8618620373879  Email: 464560351@qq.com

Testermeter-NDIR CO2 Sensor Transmitter with BACnetG01-CO2-N Series
Testermeter-NDIR CO2 Sensor Transmitter with BACnetG01-CO2-N Series
Testermeter-NDIR CO2 Sensor Transmitter with BACnetG01-CO2-N Series
Testermeter-NDIR CO2 Sensor Transmitter with BACnetG01-CO2-N Series

Testermeter-NDIR CO2 Sensor Transmitter with BACnetG01-CO2-N Series

2024-08-03 14:02:37  

Testermeter-NDIR CO2 Sensor Transmitter with BACnetG01-CO2-N Series

  • Main Feature :
  • Serial No. : Lisa0640
Contact Us For QuotationEmail:  464560351@qq.comWhatsapp&Wechat:+8618620373879

Testermeter-NDIR CO2 Sensor Transmitter with BACnetG01-CO2-N Series

overview

BACnet CO2 transmitter with temperatue and relative humidity detection, white backlit LCD displays clear readings. It can provide one, two or three 0-10V / 4-20mA linear outputs to control a ventilation system, BACnet MS/TP connection was integrated to BAS system. The measuring range can be up to 0-50,000ppm.

FEATURES

1.BACnet communication
2.CO2 detection with 0~2000ppm range
3.0~5000ppm/0~50000ppm range selectable
4.NDIR infrared CO2 sensor with More than 10 years lifetime
5.Patented self-calibration algorithm
6.Optional temperature and humidity detection
7.Provide up to 3xanalog linear outputs for measurements
8.Optional LCD display of CO2 and temperature and humidity
9.24VAC/VDC power supply
10.EU standard and CE-approval


TECHNICAL SPECIFICATIONS

CO2 Measurement
Sensing elementNon-Dispersive Infrared Detector (NDIR)
CO2 range0~2000ppm/0~5,000ppm/0~50,000ppm optional
CO2 Accuracy±30ppm + 3% of reading @22℃(72℉)
Temperature dependence0.2% FS per℃
Stability<2% of FS over life of sensor (15 year typical)
Pressure dependence0.13% of reading per mm Hg
CalibrationABC Logic Self Calibration Algorithm
Response time<2 minutes for 90% step change typical
Signal updateEvery 2 seconds
Warm-up time2 hours (first time) / 2 minutes (operation)

Temperature

Humidity

Measuring range0℃~50℃(32℉~122℉) (default)0 -100%RH
Accuracy±0.4℃ (20℃~40℃)±3%RH (20%-80%RH)

 

Display resolution0.1℃0.1%RH
Stability<0.04℃/year<0.5%RH/year
General Data
Power supply24VAC/VDC±10%
Consumption2.2 W max. ; 1.6 W avg.
 


Analog outputs

1~3 X analog outputs


0~10VDC(default) or 4~20mA (selectable by jumpers) 0~5VDC (selected at placing the order)

Operation conditions0~50℃(32~122℉); 0~95%RH, non condensing
Storage conditions10~50℃(50~122℉)


20~60%RH

Net Weight250g
Dimensions130mm(H)×85mm(W)×36.5mm(D)
Installationwall mounting with 65mm×65mm or 2”×4”wire box
Housing and IP classPC/ABS fireproof plastic material, protection class: IP30
StandardCE-Approval



Telephone
Email
Map
QQ Chat