overview

Carbon dioxide transmitter with 0~10V/4~20mA output, its six LED lights is optional for indicating six ranges of CO2. It’s designed for applications in HVAC, ventilation systems, offices, schools, and other public places. It features a Non-Dispersive Infrared (NDIR) CO2 sensor with Self-Calibration, and 15 years lifetime with high accuracy.
The transmitter has a RS485 interface with 15KV anti-static protection, and its the protocol is Modbus MS/TP. It provides an on/off relay output option for a fan control.

FEATURES

Real-time detecting CO2 level.
NDIR infrared CO2 module inside with Self-Calibration
Algorithm and more than 10 years lifetime
Wall-mounting
One analog output with voltage or current selectable
Special “L” series with 6 lights indicates six CO2 ranges and makes CO2 level show clearly.
Design for HVAC, ventilation systems, offices, schools or other public places.
Modbus RS485 communication interface optional:
15KV antistatic protection, independent address setting
CE-Approval
For more other products such as duct probe CO2 transmitter, CO2+ Temp.+ RH 3 in 1 transmitter and CO2+VOC monitors, please see our website www.IAQtongdy.com

TECHNICAL SPECIFICATIONS

General Data

 Gas detectedCarbon Dioxide (CO2)
 Sensing elementNon-Dispersive Infrared Detector (NDIR)
Accuracy@25℃(77℉),2000ppm±40ppm + 3% of reading
 Stability<2% of FS over life of sensor (15 yr typical)
 Calibration intervalABC Logic Self Calibration System
 Response time<2 minutes for 90% step change
 Warm up time 2 hours (first time)
2 minutes (operation)
CO2 measuring range0~2,000ppm OR 0~5,000ppm
6 LED lights
(just for TSM-CO2-L series)
From left to right:
Green/Green/Yellow/Yellow/Red/
Red
1 st green light on as CO2 measurement≤600ppm
1 st and 2 nd green lights on as CO2 measurement>600ppm and≤800ppm
1 st yellow light on as CO2 measurement>800ppm and≤1,200ppm
1 st and 2 nd yellow lights on as CO2 measurement>1,200ppm and≤1,400ppm
1 st red light on as CO2 measurement>1,400ppm and≤1,600ppm
1 st and 2 nd red lights on as CO2 measurement>1,600ppm