China Testing Instruments Manufacturer,Whatsapp/Wechat:+8618620373879  Email: 464560351@qq.com

Testermeter- JDG-Z Overhead live line fault indicator, fault passage indicator(FPI),Permanent Fault,Transient Fault,Earth Fault
Testermeter- JDG-Z Overhead live line fault indicator, fault passage indicator(FPI),Permanent Fault,Transient Fault,Earth Fault
Testermeter- JDG-Z Overhead live line fault indicator, fault passage indicator(FPI),Permanent Fault,Transient Fault,Earth Fault
Testermeter- JDG-Z Overhead live line fault indicator, fault passage indicator(FPI),Permanent Fault,Transient Fault,Earth Fault

Testermeter- JDG-Z Overhead live line fault indicator, fault passage indicator(FPI),Permanent Fault,Transient Fault,Earth Fault

2025-03-02 22:04:00  

JDG-Z Overhead live line fault indicator, fault passage indicator(FPI),Permanent Fault,Transient Fault,Earth Fault

  • Main Feature :
  • Serial No. : Zoe690
Contact Us For QuotationEmail:  464560351@qq.comWhatsapp&Wechat:+8618620373879

Testermeter- JDG-Z Overhead live line fault indicator, fault passage indicator(FPI),Permanent Fault,Transient Fault,Earth Fault

 

Characteristic:

The shell using high strength and high transparency aeronautical material Fully Fashioned, and treated with nanotechnology, better perspectivity. resist filth, anti-aging, without maintenance, long service life.

Built-in high performance lithium battery, Service life can reach more than eight years.

The circuit board using special chip and MCU etc imported components. Theshell made from aeronautical material and nano materials.

Theclamp with nickel plating process, best magnetic conductivity, Install and Remove with Electricity.

Fault indication turn card with strong visual,it can clear instructions with light in the night, and the color not fade under sun ultraviolet light for a long time.

 


Function and Benefit

Indicate the fault line and fault point quickly, lessen the blackout area;

Shorten troubleshooting time,improving electricity and power supply reliability;

Accurately indicate the instant fault, which is conducive to rule out the power supply problems;

Providing technical means for find the hidden permanent fault point; Shorten the search time to find the fault point, reduce the labor intensity of line patrol person;

Defining the responsibility of the fault area and responsible people; Avoiding traditional multiple switch out,switch on,line patrol to the effects of power equipment.

 

Technical Parameter

Parameter Items

Parameter Name

Parameter Details

Electrical Parameter

Short circuit fault action current

100A (Default , Can be set before delivery)

Earth fault action current

20A (The default injection method of grounding , Can be set before delivery)


Applicable line voltage

6 ~ 36 kV


Applicable line current

5~700A (Default)


Applicable power frequency

50Hz/60Hz (According customer’s request)



Maximum short circuit current

25kA/4s


Short circuit recognition time

0.02~5s


Load measurement accuracy

±3%


Power supply mode

3.6V 2.4A Lithium battery + Self-charging from the cable(The line current ≥20A)


Static power loss

≤7μA


Action power loss

< 20 mA


Minimum activate current

Insulated cable ≥10A Bare cable ≥0A


Auto reset mode

Time reset:4,8,12,24,36,48,72 Hours (Can be set before delivery, Default 12H) Auto reset after the power line recover


Action times

≥5000 Times


Continuous flash time

≥3000H


Indication

Red flag+ red LED flash

Engineering Parameter

Visibility angle

360° 50 m day time, 300 m night time

Flash time interval

Short circuit one time per 3s±10% Earth fault two times per 3s±10%


Ambient temperature

-40 ℃~ +85 ℃


Relative humidity

≤95%


Applicable wire diameter

16mm~40mm


Maximum wind speed

≤40m/s


Applicable altitude

≤5000m


Fault alarm accuracy

≥95%


Protection class

IP68


Working life

≥10 Years


MTBF

60000 H


Weight

500g ±10%


Dimensions

Ф75mm* 145mm



_20250228200855.png 



Telephone
Email
Map
QQ Chat