  • Main Feature :
  • Serial No. : Lisa0641
Contact Us For QuotationEmail:  464560351@qq.comWhatsapp&Wechat:+8618620373879

Testermeter-TGP Carbon Dioxide Transmitter with Temp.&RH

overview

It is mainly used in the application of BAS in industrial buildings to real time monitoring carbon dioxide level, temperature and relative humidity. Also suitable for applications in plant areas such as mushroom houses. The lower right hole of the shell can provide expandable use. The external sensor probe to avoid internal heating of the transmitter from affecting measurements. White backlight LCD can display CO2, Temp and RH if required. It can provide one, two or three 0-10V / 4-20mA linear outputs and a Modbus RS485 interface.

FEATURES

1.Real-time detect CO2 level of indoor environment
2.NDIR infrared CO2 sensor with Self-Calibration and up to 15 years lifetime
3.Humidity and temperature detection optional
4.Combined temperature and humidity sensor provide the highest accuracy in full range
5.Wall mounting with the external sensor probe with the higher accuracy of measurements
6.Backlit LCD display option can display CO2 measurement and temperature+ RH measurements
7.Providing one or three 0~10VDC or 4~20mA or 0~5VDC analog outputs
8.Modbus RS485 communication interface makes usage and test more convenient
9.Smart structure with the simple installation and wiring
10.CE-Approval

TECHNICAL SPECIFICATIONS

CO2 SensorNon-Dispersive Infrared Detector (NDIR)
Measurement Range0~2000ppm (default)


0~5000ppm selectable

Accuracy±60ppm + 3% of reading @22℃(72℉)
Stability<2% of full scale over the life of the sensor
CalibrationSelf-calibration system
Response Time<5 minutes for 90% step change at low duct speed
Non-linearity<1% of full scale @22℃(72℉)
Pressure Dependence0.135% of reading per mm Hg
Temperature Dependence0.2% of full scale per ºC
Temperature & Humidity SensorTemperatureRelative Humidity

 

Sensing element:Band-gap-sensorCapacitive humidity sensor
Measuring range0℃~50℃(32℉~122℉) (default)0 ~100%RH
Accuracy±0.5℃ (0℃~50℃)±3%RH (20%-80%RH)
Display resolution0.1℃0.1%RH
Stability±0.1℃per year±1%RH per year
General Data
Power supply24VAC/24VDC ±5%
Consumption1.8 W max. ; 1.0 W avg.
 


LCD display

White backlit LCD display CO2 measurement


or CO2 + temperature& humidity measurements

 


Analog output

1 or 3 X analog outputs


0~10VDC(default) or 4~20mA (selectable by jumpers)

0~5VDC (selected at place the order)

Modbus RS485 Interface19200bps, 15KV antistatic protection.
Operation conditions0℃~50℃(32~122℉); 0~99%RH, non condensing
Storage conditions0~60℃(32~140℉)/ 5~95%RH
Net weight300g
IP classIP50
Standard ApprovalCE-Approval