China Testing Instruments Manufacturer,Whatsapp/Wechat:+8618620373879  Email: 464560351@qq.com

Testermeter- SKIM400 Insulation Monitoring Device below AC400V

Testermeter- SKIM400 Insulation Monitoring Device below AC400V

2024-11-27 23:36:49  

SKIM400 Insulation Monitoring Device below AC400V

  • Main Feature :
  • Serial No. : Zoe551
Contact Us For QuotationEmail:  464560351@qq.comWhatsapp&Wechat:+8618620373879

Testermeter- SKIM400 Insulation Monitoring Device below AC400V

 

SKIM400 is an insulation monitoring device for IT system main circuits and control circuits below AC, DC and AC/DC 400V. SKIM400 can only perform insulation monitoring independently and cannot be combined with the insulation fault location.


Insulation Monitoring Device for IT system

Model*

SKIM200

SKIM400

SKIM600M

SKIM600FL

SKIM600H

Main circuits

X

Control circuits

DC

-

400V

400V

400V

-

AC

230V

400V

690V

690V

1140V

DC/AC

230V

400V/400V

400V/690V

400V/690V

1140V

IFL system

X

X

X

X


SKIM400 Features:

1. Applicable to IT systems main circuits and control circuits below AC/DC 400V
2. Internal/external testing/reset buttons
3. Automatic and manual reset functions
4. Multi type, wide range control power input
5. Humanized and easy to operate interface, which can display various parameters and system leakage capacitance
6. DIN rail installation method
7. LCD screen display with backlight
8. Measure and display the insulation resistance of ungrounded systems
9. Measurement and display of leakage capacitance (C)
10. Communication via Modbus RS-485
11. Adjustable response delay
12. Two independent alarm relays (each relay has a switching contact)
13. N/O or N/C operation (optional)


SKIM400 Specification

Item

Value

IT system Rated Voltage

230V

Power supply

AC 85-265V, DC18-36V

Alarm Value Ran 1

19999 kΩ

Response time at R=0.5xRan and G=1 μ F

4s

Insulation Alarm Delay

09999s

Measure Voltage(U1)

50V

Internal Resistance (R1)

152 kΩ

Resistance Measurement Range

1kΩ~20MΩ

Resistance Measurement Range

1kΩ~20MΩ

Measurement Accuracy(1~5 kΩ)

1 kΩ

Measurement Accuracy(5 kΩ~1MΩ)

+15 %

+15 %Permissible Leakage Capacitance (Ce)

≤ 200 μF(Distributed capacitance curve in the manual)

 

 



Telephone
Email
Map
QQ Chat