China Testing Instruments Manufacturer,Whatsapp/Wechat:+8618620373879  Email: 464560351@qq.com

TesterMeter-ETCR2800N Built-in Grounding Resistance Online Tester,Online earth resistance tester,GEO Meter
TesterMeter-ETCR2800N Built-in Grounding Resistance Online Tester,Online earth resistance tester,GEO Meter
TesterMeter-ETCR2800N Built-in Grounding Resistance Online Tester,Online earth resistance tester,GEO Meter
TesterMeter-ETCR2800N Built-in Grounding Resistance Online Tester,Online earth resistance tester,GEO Meter
TesterMeter-ETCR2800N Built-in Grounding Resistance Online Tester,Online earth resistance tester,GEO Meter
TesterMeter-ETCR2800N Built-in Grounding Resistance Online Tester,Online earth resistance tester,GEO Meter

TesterMeter-ETCR2800N Built-in Grounding Resistance Online Tester,Online earth resistance tester,GEO Meter

2023-07-05 21:54:49  

Built-in Online Earth Tester

  • Main Feature : 1. On - line monitoring the earth resistance of grounding system 2. Measure Range: 0.010Ω~100Ω 3. Equip with RS485( support MODBUS-RTU communication protocol) or GPRS interface 4. can be built into inside case of other equipment ,convenient the secondary development and integration by users 5. Network system can be built to realize real-time detection and remote monitoring
  • Serial No. :
Contact Us For QuotationEmail:  464560351@qq.comWhatsapp&Wechat:+8618620373879

TesterMeter-ETCR2800N Built-in Grounding Resistance Online Tester,Online earth resistance tester,GEO Meter

INTRODUCTION

TesterMeter-ETCR2800N Non-contact Earth Resistance On-line Monitor is high-tech product that our company has devoted to "grounding resistance detection technology research" for more than ten years, specialize for online monitoring grounding down lead connection status, circuit grounding resistance and metal circuit connection resistance. On-line testing, non-contact measurement, grounding wire pass through the perforation of the detector, definitely will not influence grounding effective for lightening and normal operation, no need the self-inspection, real time on-line testing. Provide RS485 wire communication (support MODBUS-RTU communication protocol) , The monitor is composed of sensor and PCB module, which is suitable for user secondary development integration.

TesterMeter-ETCR2800N Non-contact Earth Resistance On-line Monitor suitable for transmission line tower grounding; Meteorological lightning protection grounding; Petrochemical grounding; Communication grounding; Substation grounding; Railway facilities grounding; Construction warehouse grounding; Metal circuit resistance; Electrical equipment grounding and others place. It can also be used for anti-theft monitoring of grounding wires and metal cables.

TesterMeter-ETCR2800N Non-contact Earth Resistance On-line Monitor can install and use singly, and also can set up wired or wireless network system.

TesterMeter-ETCR2800N Accessories:

图片关键词

  • Detector

  • PCB Module

  • Connection Wire

  • Warranty card/Qualification card

  • Paper Box

SPECIFICATION

Technical Parameters

FunctionDescription
  Function Loop circuit grounding resistance on-line monitoring, metal return circuit resistance connection online monitoring, grounding condition monitoring. anti-theft monitoring of grounding wires and metal cables
Power Supply Detector:6VDC~9VDC,50mA Max(external power supply).
Resistance  Range 0.01Ω~100Ω
Resolution 0.001Ω
Accuracy ±2%rdg±3dgt(20℃±5℃,below 70%RH)
PCB Size 122mm×56mm×20mm
Sensor Size 110mm×80mm×55mm
Sensor Perforation Size 65mm×36mm
Sensor Weight 595g;
Overflow Indication Test data>100Ω, communication send “OLΩ” command
PCB Interface J1:Signal output, power input interface     
J2:Sensor and PCB interface
Symbol J1 P+:Power input with positive R+:Signal output with positive
P-:Power input ground   R-: Signal output with negative
GND:Signal ground, short connect with power input ground (P-)
Symbol J2 I+、I-Current coil interface U+、U-Voltage coil interface
GND:Common ground
Connect Wire 1pcs ,0.5 meter length(5 core wire)
  Line Wire1pcs ,1 meter length(5 core wire)
Connection Identifier Red---power supply input anode;
Black--- power supply input cathode;
Green---RS485 signal anode;
Yellow---RS485 signal cathode;
White--- grounding wire shield
(power supply input cathode can connects with analog grounding by short circuit connection)
Communication method RS485 communication protocol(support MODBUS)
GPRS communication (optional)
Working Temperature And Humidity -20℃~55℃; 20%RH~90%RH
Shift Automatic shift
Grounding lead Interference Current Should be avoid
External Magnetic Field <40A/m
External Electric Field <1V/m
Single Measurement time About 0.5 second
Working current 50mA Max.
Installation The ground wire goes through the center hole of the sensor
Installation Demand PCB should install into other protective case

APPLICATION

Network Structure

Wired Network System (Self -Development Software)

Wired network system through RS485 communication protocol to transmit data, build up by the detector, 【communicator, monitoring software, power adapter, computer (above equipment need the user provide and secondary development) 】and so on, suitable for short-distance 1500 meters grounding resistance monitoring.


  • Wireless Network System (Self -Development Software)


Wireless network system through GPRS communication protocol to transmit data ,build up by the detector(built-in GPRS transceiver module), 【SIM communication card, monitoring software, power adapter, computer(above equipment need the user provide and secondary development)】 and other components for long-distance ground resistance monitoring., distance is not limited.


Principle & Application

  • Test Principle

TesterMeter-ETCR2800 Non-contact Earth Resistance On-line Monitor, the basic principle of measuring the grounding resistance is to measure the loop resistance. Firstly sensor send out a drive pulse signal to the measured ground return circuit, then measured ground return circuit responses a pulse electromotive force E, under the influence of electromotive force E will generate current I in the be measured ground return circuit. Sensor measures E and I value, and gets resistance value of be measured ground return circuit through the formula: R=E/I.




  • Loop Resistance & Metal Loop Connection Resistance Tesing

图片关键词

Loop resistance is a composite value includes A point grounding resistance value, grounding down lead metallic conductor’s resistance value, metal overhead line’s resistance value, connection resistance value (contact resistance) between grounding down lead and metal overhead line, B point grounding resistance value.

If grounding network A and grounding network B up and down are connected together on the ground, Detector measures out the resistance value of metal return circuit is very small in general situation, only few of and less than one Ohm, this is the metal loop connection resistance, as a equipotential resistance, but not grounding resistance. Therefore the detector is much convenient to test metal return circuit connection resistance.






  • Test Method

Single point grounding system: If between grounding network A and grounding network B haven`t overhead line, and not connect together on the ground, then grounding network A and grounding network B can regard as standalone single point grounding connection. Detector cannot test the grounding resistance of single point grounding system directly, will display “OL” overload symbol. Therefore it needs adding one or more auxiliary grounding electrode, to form multipoint loop circuit.

Three point grounding system: In the following figure, the tested ground pole is A and the other two auxiliary ground pole is B and C. The poles A, B, C are connected together on the ground. In the three ground poles grounding down leads were installed on a detector, can accurately test the ground point A resistance value.

Calculated as follows:

R1=RA+RB//RC-------- (1);

R2=RB+RA//RC-------- (2);

R3=RC+RA//RB-------- (3).

Related Series Model

ModelCT StructureRangeDifference
TesterMeter-ETCR2800BClose loop0.010Ω~200ΩNO LCD and Indicator light, need to build Internet
TesterMeter-ETCR2800CClose loop0.010Ω~200ΩWith LCD, Alarm Setting,Sound and light alarm indication
TesterMeter-ETCR2800KBSplit-core0.010Ω~100ΩNo need to disconnect the grounding wire in installing,detector with sound and light alarm indication
TesterMeter-ETCR2800KCSplit-core0.010Ω~100ΩNo need to disconnect the grounding wire in installing, detector with LCD, Alarm Setting, sound and light alarm indication
TesterMeter-ETCR2800NClose loop and built-in type0.010Ω~100ΩNo shell, suitable for secondary development
TesterMeter-ETCR2800T Close loop0.01Ω~100ΩAdopts 304 stainless steel shell, internal filling and sealing with resin, strong structure, anti-explosion, anti-impact, high and low temperature resistance, waterproof and dustproof.


Telephone
Email
Map
QQ Chat