TesterMeter-Battery Discharge Load Tester HDGC3980
General information
HDGC3980 Battery Discharge Load Tester can be used as the discharge load in the battery off-line state to realize the constant discharge at the set value by regulating continuously the discharge current. When discharging, the tester will automatically stop discharging when the voltage on the battery group terminal or the cell falls to the set lower limit value, or when the set discharging time is out, or when it reaches the set discharging capacity. Battery Discharge Tester can records all valuable and continuous real-time data during the discharge process. This tester system is simple, safe and accurate for monitoring voltage of cells adopting wireless connection. |
Features
● PTC ceramic resistor is adopted to avoid the red heat phenomenon for a safer discharge process . ● Intelligent SCM ARM control, 7inch 1024*600 LCD screen , capacitive touch operation, built in English menu, simple and clear operation menu. ● Automatic self-protection stop function, over-heat protection ,over voltage protection , over current protection and reverse connection protection ,alarm prompt is displayed on the screen once it appears any issue, air circuit breaker automatically cut off . ● It can set discharge termination condition including cell low voltage,whole group voltage low/high, charge current low, charge/discharge time , charge/discharge capacity ●.When any condition can be met, the instrument can stop automatically testing with buzz sound and record the stop reason at the same time. ● It can evaluate the capacity of discharge test time . |
Technical parameter
Applicable battery | DC 220V battery pack | |||
Discharge Voltage Range | DC 176-264V | |||
Discharge Current Range | 0-200A | |||
Working mode | Standalone mode, parallel master mode, parallel slave mode, and remote controlled mode | |||
Protection performance | Battery test overvoltage protection, undervoltage stop, overcurrent protection, reverse wiring protection, 65℃ overtemperature protection, with LCD prompt and buzzer alarm | |||
Control precision | Discharge current≤±1%; group terminal voltage≤±0.1%; cell voltage≤±0.1% | |||
PC communication | RS485 interface, USB interface | |||
Data storage capacity | Built-in SD card with a capacity of 8G and the USB flash drive with a capacity of 16G | |||
Work Environment | ||||
Cooling | Forced air cooling | |||
Temperature | Working rage: -5-50℃ Storage temperature: -40-70℃ | |||
Humidity | Relative humidity 0-90% (40±2℃) | |||
Altitude | Altitude 4,000m | |||
Noise | ﹤75dB | |||
Working Power Supply | ||||
Voltage | Power supply: single-phase AC220V (-20%-+30%), frequency: 45-65Hz; charging power supply: refer to nameplate parameters or case label | |||
Dielectric Withstand Test | Input-housing: 2200Vdc 1min Input-output: 2200Vdc 1min Output-housing: 700Vdc 1min | |||
Safety | Compliance with EN610950 |